EasyManua.ls Logo

Siemens SIRIUS 3RT - Page 115

Siemens SIRIUS 3RT
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
6.10 Contactors with extended operating range
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
115
Other contactors with extended operating range
As well as the contactors with solid-state operating mechanisms approved according to IEC
60077-2, contactors and contactor relays with conventional operating mechanisms and
series resistors in the form of a coil circuit are also available. These devices have an
operating range of 0.7 - 1.25 x U
s
, and a temperature range of -4 C to +70° C.
The series resistor is installed in an attached module. The NC auxiliary contact is integrated
into the basic unit and is already fully wired. Expansion with 4-pole auxiliary switches on the
front is possible for contactors and contactor relays. The contactors can be additionally
expanded with lateral auxiliary switches.
Size
Article number
Power rating of three-phase motors [kW]
at 400 V
-
3RH2122-2K.40-0LA0
-
S00 3RT201.-2K.42-0LA0 5.5
Coupling relays
In sizes S00 and S0, coupling relays (motor contactors and contactor relays) with the
extended operating range 0.7 - 12.5 x U
s
are additionally available.
The coupling relays in size S0 are connected with varistors.
For a temperature range of 60° C to 70° C, the minimum clearance is 10 mm.
It is not possible to fit the 3RH coupling relays with auxiliary switches.
Size
Article number
Power rating of three-phase motors [kW]
at 400 V
-
3RH2…-2L…
-
S00 3RT2.1.-2K… 5.5
S0
3RT2.2.-2K…
15