Configuration
6.13 Starting three-phase motors with reduced starting current peaks (contactor assembly for star-delta (wye-
delta) start)
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
151
Table 6- 9 Spring-loaded connection
Rated data for 50 Hz
400 V AC
Size
Article number
Power [kW]
Operational
current
I
e
[A]
Motor current
[A]
Line / delta con-
tactor
Star contactor
Complete assembly
5.5
12
9.513.8
S00-S00-S00
3RT2015-2....
3RT2015-2....
3RA2415-8XF31-2...
7.5
16
12.117
3RT2017-2....
3RT2015-2....
3RA2416-8XF31-2...
11 25 1925 3RT2018-2.... 3RT2016-2.... 3RA2417-8XF31-2...
11
25
1925
S0-S0-S0
3RT2024-2...0
3RT2024-2...0
3RA2423-8XF32-2...
15
32
24.134
3RT2026-2...0
3RT2024-2...0
3RA2425-8XF32-2...
18.5
40
34.540
3RT2026-2...0
3RT2024-2...0
3RA2425-8XF32-2...
22
50
3143
3RT2027-2...0
3RT2026-2...0
3RA2426-8XF32-2...
22 / 30
45 / 60
3143
S2-S2-S0
3RT2035-3...0
3RT2026-2...0
--
37
80
62.1 ... 77.8
3RT2035-3...0
3RT2027-2...0
--
45
86
69 ... 86
3RT2036-3...0
3RT2028-2...0
--
55
115
77.6 ... 108.6
S2-S2-S2
3RT2037-3...0
3RT2035-3...0
--
55
115
77.6 ... 108.6
S3-S3-S2
3RT2045-3...0
3RT2035-3...0
--
75
150
120.7 ... 150
3RT2045-3...0
3RT2036-3...0
--
90
160
86 ... 160
3RT2046-3...0
3RT2037-3...0
--
Note
The selection of contactor types refers to a fused design.
Connection example with spring-loaded connection and large conductors, e.g. with 6 mm
2
connection
cross-section
For a contactor assembly for star-delta (wye-delta) start, e.g. 3RA2426-8XH32-2BB4
(22 kW, 50 A), it is possible to select the following connection type with a 6 mm
2
conductor
cross-section:
Remove the upper wiring modules to connect the main current paths between line
contactor (Q 11) and delta contactor (Q 13).
Separate infeed of line contactor (Q 11) and delta contactor (Q 13) with 6 mm
2
(permitted
in a three-way network).
Two conductors per phase with 6 mm
2
conductor cross-section are connected to the
central infeed short-circuit protection device and only one conductor per phase to the
contactors.