Switching overvoltage - surge suppressor
Overvoltages when switching off contactors (inductive load) can cause faults in electronic
devices (timing relays, PLCs, coupling modules) in the same network if the contactors are
used without the appropriate filters.
Table 9- 18 Switching overvoltage - surge suppressor
DC Forward voltage
(U
D
= ~1 V)
Very high (6-9x)
• Non-critical
dimensioning
• Lowest induction
voltage
• Very simple and
reliable
• Low-cost
• Long drop-out
delay
• Short-circuit on
failure
AC/DC Breakdown
voltage (U
BR
)
Very low
• Non-critical
dimensioning
• Simple design
• Protected against
reverse polarity
• Short pick-up time
No attenuation below
the breakdown voltage
(U
BR
)
DC Breakdown
voltage (U
BR
)
Very low
• Non-critical
dimensioning
• Simple design
• Short pick-up time
No attenuation below
the breakdown voltage
(U
BR
)
AC/DC Varistor voltage
(U
Varistor
)
Very low
• Non-critical
dimensioning
• High energy
absorption
• Very simple design
No attenuation below
U
Varistor
AC/DC U
RC
Very low
• HF attenuation
through energy
storage
• Immediate shutdown
• Extremely suitable for
AC
• Exact dimensions
required
• Expensive