Configuration
6.3 Operating mechanism system / coil selection 3RT contactors and 3RH2 contactor relays
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
76 Manual, 09/2017, A5E03656507120A/RS-AE/006
Connecting the supply voltage
The supply voltage for the solenoid operating mechanism must be connected to A1/A2.
Note
The slide switch on the front side of the withdrawable coil must be switched to the "ON"
position before commissioning (factory default setting is "OFF").
Connecting the 24 V DC control signal
The control signal is connected via a 2-pin plug-in connection on the front side of the
withdrawable coil (the spring-loaded connector is included in the scope of supply). The
connector is labeled with the polarity.