EasyManua.ls Logo

Siemens SIRIUS 3RT - Page 80

Siemens SIRIUS 3RT
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
6.3 Operating mechanism system / coil selection 3RT contactors and 3RH2 contactor relays
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
80 Manual, 09/2017, A5E03656507120A/RS-AE/006
"Remaining lifetime RLT" signal
Upon reaching a remaining lifetime of 20 %, the "remaining lifetime RLT" signal is available
at terminals R1/R2 via a floating relay contact (NO contact, hard gold-plated, enclosed) and
can be input to SIMOCODE, PLC or other devices for processing, for example. Permissible
current-carrying capacity of the R1/R2 relay output:
I
e
/AC-15 at 24 ... 230 V: 3 A
I
e
/DC-13 at 24 V: 1 A
Control
The contactors can be controlled as follows:
via a 24 V DC control signal
via relay outputs, e.g. of PLC, SIMOCODE.
Power supply
To supply the solenoid operating mechanism and the remaining lifetime signal with power,
the control supply voltage U
s
must be connected to terminals A1/A2 of the laterally mounted
electronic module.
Control inputs
The control inputs of the contactor are connected to a 7-pole plug-in connection (the spring-
loaded connector is part of the scope of supply).
Changeover from automatic to local control
Automatic control can be changed over to local control via inputs H1/H2. During
commissioning or in the event of a fault, for example, automatic control via PLC or
SIMOCODE can be deactivated and the contactor can be controlled manually.

Table of Contents

Related product manuals