Operator control functions via PROFIBUS
7.4 Settings
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
107
The transducer can handle numerous measurement tasks. You only have to make the
following settings:
● Settings with a configuration tool, for example STEP 7 or HW Config: Here, you choose
the desired configuration with which the cyclically transmitted user data will be structured.
● Settings with SIMATIC PDM: Here you set the parameters that also influence the cyclic
user data.
Configuration of user data (Page 159)
If you set a new device, select the measurement type, for example pressure or fill level. As a
result, you will see the appropriate default parameter settings in the SIMATIC PDM user
interface. The following sections will introduce only those which you will still have to set.
To read out the settings, proceed as follows:
1. Start the "Download to PG/PC" function.
The current settings are downloaded to the device.
2. Check the current settings.
3. Change the necessary settings.
4. Load the parameter settings into the device.
5. Save the parameter settings offline.
Pressure measurement
Procedure
To select pressure measurement, proceed as follows:
1. Start SIMATIC Manager.
2. Create a device with the desired measurement type.
3. To open SIMATIC PDM, double-click on the device you have created.