Operator control functions via PROFIBUS
7.4 Settings
SITRANS P DS III with PROFIBUS PA
108 Operating Instructions, 06/2013, A5E00053276-07
7.4.4
Level measurement
Procedure
To set fill level measurement, proceed as follows:
1. Start SIMATIC Manager.
2. Create a device with measurement type "Fill level".
3. To open SIMATIC PDM, double-click on the device you have created.
Depending on whether you want to measure a height, a volume, or a mass, set the following
values.
Height measurement
To select height measurement, proceed as follows:
Start SIMATIC PDM. Create an assignment between the pressure to be measured
(measurement range) and the fill level to be recorded (working range), by setting these
parameters:
>
Input
>
>
Transducer block 1
Transmitter type:
Level
>
>
>
Measuring range
Start of scale value
Full scale value
>
>
>
Working range
Unit:
Unit of length [m, cm, mm, ft, in, yd]
Start of scale value
Full scale value
Create an assignment between the measured level value and the output value by setting
these parameters:
>
Output
>
>
Function block 1 - analog input
Channel:
Measured value (primary variable)
>
>
>
Measured value scaling
Start of scale value:
Full scale value:
as in "working range"
as in "working range"
>
>
>
Output scaling
Unit:
Start of scale value:
Full scale value:
a
s in "working range"
as in "working range"
as in "working range"