Operator control functions via PROFIBUS
7.4 Settings
SITRANS P DS III with PROFIBUS PA
108 Operating Instructions, 06/2013, A5E00053276-07
Level measurement
Procedure
To set fill level measurement, proceed as follows:
1. Start SIMATIC Manager.
2. Create a device with measurement type "Fill level".
3. To open SIMATIC PDM, double-click on the device you have created.
Depending on whether you want to measure a height, a volume, or a mass, set the following
values.
To select height measurement, proceed as follows:
● Start SIMATIC PDM. Create an assignment between the pressure to be measured
(measurement range) and the fill level to be recorded (working range), by setting these
parameters:
Start of scale value
Full scale value
Unit of length [m, cm, mm, ft, in, yd]
● Create an assignment between the measured level value and the output value by setting
these parameters:
Function block 1 - analog input
Measured value (primary variable)
Start of scale value:
Full scale value:
Start of scale value:
Full scale value:
s in "working range"