Description
3.6 Principle of operation
SITRANS P DS III with PROFIBUS PA
34 Operating Instructions, 06/2013, A5E00053276-07
Measuring cell for gauge pressure, front-flush membrane
Reference pressure opening
Figure 3-12 Function chart of the measuring cell for gauge pressure, flush mounted diaphragm
The inlet pressure (p
e
) is transferred to the gauge pressure sensor ⑥ via the seal diaphragm
④ and the filling liquid ⑤, displacing its measuring diaphragm. The displacement changes
the resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The
change in the resistance causes a bridge output voltage proportional to the inlet pressure.
Transmitters with measuring span ≤ 63 bar measure the inlet pressure against atmosphere,
those with measuring spans ≥ 160 bar against vacuum.
Measuring cell for absolute pressure, front-flush membrane
Figure 3-13 Function chart of the measuring cell for absolute pressure, flush mounted diaphragm