3.6 Principle of operation
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
31
3.6.3.3
Measuring cell for level
Pressure cap
Seal diaphragm on the measuring cell
O-ring
Filling liquid of the measuring cell
Measuring cell body
Capillary tube with the fill fluid of the mounting
flange
Overload diaphragm
Flange with a tube
Differential pressure sensor
Seal diaphragm on the mounting flange
Figure 3-9 Function chart of the measuring cell for level
The inlet pressure (hydrostatic pressure) works hydraulically on the measuring cell
through the seal diaphragm
on the mounting flange .
Differential pressure at the measuring cell is transmitted to the differential pressure
sensor
through the seal diaphragms and the filling liquid .
When measuring limits are exceeded, the overload diaphragm
is displaced until one of
the seal diaphragms
or rests on the measuring cell body . The seal diaphragms
⑥ thus protect the differential pressure sensor
from overload.
The seal diaphragm
is displaced by the differential pressure. The displacement
changes the resistance of the four doped piezoresistors in the bridge circuit.
The change in the resistance causes a bridge output voltage proportional to the
differential pressure.