Installing / mounting
4.3 Installation (except level)
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
45
4.3
Installation (except level)
4.3.1
Installation mounting (except for level)
Requirements
Note
Compare the desired operating data with the data on the nameplate.
Please
also refer to the information on the remote seal if this is fitted.
Note
Protect the transmitter against:
Direct heat radiation
Rapid temperature fluctuations
Heavy contamination
Mechanical damage
Direct sunlight
Note
The housing may only be opene
d for maintenance, local operation or to make electrical
connections.
The installation location is to be as follows:
Easily accessible
As close as possible to the measuring point
Vibration-free
Within the permitted ambient temperature values
Installation configuration
The transmitter may in principle be configured above or below the pressure tapping point.
The recommended configuration depends on the medium.
Installation configuration for gases
Install the transmitter above the pressure tapping point.
Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any
condensate produced can drain in the main line and thereby avoid corruption of the
measured values.