Functional safety
8.7 PROFIsafe
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
139
Import EDD with SIMATIC PDM (Page 139)
Configure CPU with HW Config (Page 139)
Configure device with HW Config (Page 139)
Configure CFC (Page 142)
Import EDD with SIMATIC PDM
To import the EDD, click on "SIMATIC PDM" > "Manage Device Catalog".
Configure CPU with HW Config
The relevant settings for fail-safe of the CPU are located in the CPU-specific documentation.
If your CPU is a SIMATIC CPU, proceed as follows:
1. Double click on the CPU.
2. You are now in the "Properties" dialog box on the "Protection" tab. Activate the following
checkboxes:
– Protection level "1"
– "Removable with password"
– "CPU contains safety program"
Configure device with HW Config
Procedure
1. You are in the "Catalog" view with the "standard" profile. Go to the device in the catalog:
– "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe"
valid for firmware 0301.02.01 and 0301.02.02
– "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe
V2"
valid as of firmware 0301.02.03
u will find the valid firmware version on the label and can then select the correct
GSD file for your version.
2. Pull the following device onto "PA Master System" with Drag & Drop.
The "Properties" dialog then opens.