SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
185
Interrupts, error and system alarms
Table 12- 1 Status code
configured measured value
source
80 Electronics temperature,
sensor temperature, raw
pressure value, secondary
variable 1, secondary
variable 2, measured value
(primary variable),
secondary variable 3,
--- Normal operation ---
G_132 84 Electronics temperature,
sensor temperature, raw
pressure value, secondary
variable 1, secondary
variable 2, measured value
(primary variable),
secondary variable 3,
Good,
update.event
A parameter relevant
to the behavior of the
slave was changed.
The display goes off
after 10 sec.
Note to the control
system.
G_137 89 Output, totalizer output Good,
warning limit
Configured low
warning limit violated.
Correct error through
user program.
G_138 8A Output, totalizer output Good,
warning limit
High configured
warning limit violated.
Correct error through
user program.
G_141 8D Electronics temperature,
output, totalizer output
Good,
Configured low alarm
limit violated.
Correct error through
user program.
G_142 8E Electronics temperature,
output, totalizer output
Good,
High configured alarm
limit violated.
Correct error through
user program.
G_164 A4 Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output, totalizer
Good,
Service required
Service interval
expired: Calibrate or
service.
Service, calibration of the
electronics, or service of
the sensor cell is
necessary.
U_071 47 Output Unsure,
Last usable value,
value constant
Input condition "fail
safe" is fulfilled, the
parameterized safety
setting is set to "keep
Check the data
measurement.