3.6 Principle of operation
SITRANS P DS III with PROFIBUS PA
30 Operating Instructions, 06/2013, A5E00053276-07
3.6.3.2
Measuring cell for differential pressure and flow rate
Inlet pressure P
+
Overload diaphragm
Pressure cap
Filling liquid
O-ring
Seal diaphragm
Measuring cell body
Inlet pressure P
-
Differential pressure sensor
Figure 3-8 Function chart of the measuring cell for differential pressure and flow rate
Differential pressure is transmitted to the differential pressure sensor through the seal
diaphragms
and the filling liquid .
When measuring limits are exceeded, the seal diaphragm
is displaced until the seal
diaphragm
rests on the measuring cell body . The differential pressure sensor is
thus protected against overloading since no further deflection of the overload diaphragm
is possible.
The seal diaphragm
is displaced by the differential pressure. The displacement
changes the resistance of the four piezoresistors (bridge circuit) of the differential
pressure sensor.
The change in the resistance causes a bridge output voltage proportional to the
differential pressure.