Operator control functions via PROFIBUS
7.7 Warning and alarm limits
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
117
Table 7- 8 Combined blocks
Write block for parameter
changes over the bus
Release of local operation
over SIMATIC PDM
Locking of buttons and functions (Page 81)
The analog input function blocks each have high and low warning and alarm limits for the
output. In order to avoid unstable display of warnings and alarms, specify a hysteresis.
In the analog input function blocks, set the following parameters according to process
requirements:
● Limit value hysteresis
● High warning limit
● High alarm limit
● Low warning limit
● Low alarm limit
If limits are violated, the output is accompanied by a status which you can evaluate in your
application program:
Table 7- 9 Limits and status displays