Basic safety instructions
Danger of poisoning when the device is vented.
If toxic process media are measured, toxic gases and liquids can be released when the
device is vented.
• Before venting ensure that there are no toxic gases and liquids in the device. Take the
appropriate safety measures.
Improper commissioning in hazardous areas
Device failure or danger of explosion in hazardous areas.
• Do not commission the device until it has been mounted completely and connected in
accordance with the information in Chapter "Technical data (Page 191)".
• Before commissioning take the effect on other devices in the system into account.
Opening device in energized state
Danger of explosion in areas subject to explosion hazard.
• Only open the device in a de-energized state.
• Check prior to commissioning that the cover, cover locks, and cable inlets are
assembled in accordance with the directives.
: Devices having the type of protection "Intrinsic safety Ex i" may also be opened
in energized state in hazardous areas.