Technical data
13.2 Input point
SITRANS P DS III with PROFIBUS PA
192 Operating Instructions, 06/2013, A5E00053276-07
PROFIBUS PA and FOUNDATION Fieldbus
Span (fully adjustable) or
measuring range, max.
operating pressure (in
accordance with
97/23/EC Pressure
Equipment Directive) and
max. test pressure
(pursuant to DIN 16086)
(for oxygen
measurement, max.
100 bar and 60 °C
ambient
temperature/process
temperature
)
Span Maximum
operating
pressure
Maximum test
pressure
Measuring
range
Maximum
operating
pressure
Maximum test
pressure
0.01 …
1 bar g (0.15
4 bar g
(58 psi g)
6 bar g
(87 psi g)
1 bar g
(14.5 psi g)
4 bar g
(58 psi g)
6 bar g
(87 psi g)
0.04 …
4 bar g (0.58
7 bar g
(102 psi g)
10 bar g
(145 psi g)
4 bar g
(58 psi g)
7 bar g
(102 psi g)
10 bar g
(145 psi g)
0.16 …
16 bar g (2.3
21 bar g
(305 psi g)
32 bar g
(464 psi g)
16 bar g
(232 psi g)
21 bar g
(305 psi g)
32 bar g
(464 psi g)
0.63 … 63 bar
g (9.1 …
67 bar g
(972 psi g)
100 bar g
(1450 psi g)
63 bar g
(914 psi g)
67 bar g
(972 psi g)
100 bar g
(1450 psi g)
1.6 …
160 bar g (23
167 bar g
(2422 psi g)
250 bar g
(3626 psi g)
160 bar g
(2321 psi g)
167 bar g
(2422 psi g)
250 bar g
(3626 psi g)
4 … 400 bar g
(58 …
400 bar g
(5802 psi g)
600 bar g
(8702 psi g)
400 bar g
(5802 psi g)
400 bar g
(5802 psi g)
600 bar g
(8702 psi g)
7.0 ...
700 bar g
(102 ...
800 bar g
(11603 psi g)
800 bar g
(11603 psi g)
700 bar g
(10153 psi g)
800 bar g
(11603 psi g)
800 bar g
(11603 psi g)
• Measuring cell with
silicone oil filling
30 mbar a (0.44 psi a)
• Measuring cell with
inert liquid
30 mbar a (0.44 psi a)
Upper measuring limit 100% of max. span (max. 100 bar g
(1450 psi g) for oxygen measurement)
ambient temperature/process temperature
100% of max. measuring range (max.
100 bar g (1450 psi g) for oxygen
measurement) ambient temperature/process
Between the measuring limits (fully adjustable)