Description
3.6 Principle of operation
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
29
Flange connection in accordance with EN 61518
Flush-mounted process connections
3.6.3.1
Measuring cell for gauge pressure
Reference pressure opening
Filling liquid
Measuring cell
Gauge pressure sensor
Process connection
p
e
Inlet pressure
Seal diaphragm
Figure 3-7 Function chart of measuring cell for gauge pressure
The inlet pressure (p
e
) is transferred to the gauge pressure sensor via the seal diaphragm
and the fill fluid , displacing its measuring diaphragm. The displacement changes the
resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The
change in the resistance causes a bridge output voltage proportional to the inlet pressure.
Transmitters with measuring span ≤ 63 bar measure the inlet pressure against atmosphere,
those with measuring spans ≥ 160 bar against vacuum.