Interrupts, error and system alarms
12.2 Errors
SITRANS P DS III with PROFIBUS PA
188 Operating Instructions, 06/2013, A5E00053276-07
configured measured value
source
B_031 1F Output, totalizer output Bad,
Out of service, value
constant
Function block was
placed out of service
with a target mode
command. A
parameterized safety
For normal operation,
reset the target mode to
AUTO.
B_060 3C Output Bad;
Device is not yet in
safe state.
Complete PROFIsafe
commissioning.
1)
Only if the failure behavior of the analog input function block is set to "The incorrectly
calculated measured value is on output".
2)
Only if the failure behavior of the totalizer function block has been set to "Operation".
Error display (Page 74)
Status display (Page 76)
Status (Page 162)
Errors
Errors and error correction
Measured value shows up on
the display but is not displayed
in the control system.
• Mode 15 • Check whether the bus
address on the device
matches the bus address in
the control system. If it does
not match, correct the bus
address.
• Mode 16 • Set "ident" in mode 16.