Interrupts, error and system alarms
12.2 Errors
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
189
Table 12- 2 Error message
F_003 - Changes to the bus address and
device operating type are not
possible, since the device is in
communication with a class 1
End communication with class
1 master.
F_004 - Display overflow. Check settings of physical unit
and position of decimal point,
and adjust to the current
F_006 - Correction not successful. Check calibration span and
F_007 - After zero-point calibration,
measurements no longer
possible in entire measurement
Check measurement range,
decrease correction if
necessary.
F_008 - Local operation blocked by
SIMATIC PDM.
Use SIMATIC PDM to set the
"Local operation" parameter to
Status (Page 162)