Interrupts, error and system alarms
12.1 Overview of status codes
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
187
Display
Hex
configured measured value
source
PDM display
Cause
Measure
B_004 04 Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Configuration error
Calibration span too
small.
Repeat the calibration
procedure with pressure
values which are farther
apart.
B_011 0B Secondary variable 3 Bad,
not connected, value
constant
Variable is not
calculated
Correct the "transmitter
type" setting.
B_012 0C Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Device error
Device has an
irreparable error
Replace the electronics.
B_015 0F Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Device error, value
constant
Device has an
irreparable error
Replace the electronics.
B_016 10 Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Sensor error
Sensor indicates an
error.
Have a service technician
check the sensor.
B_017 11 Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Sensor error, limit
value violated
Negative pressure too
high. Low control limit
violated (<-20% of
nominal measurement
range).
Increase the pressure in
the positive direction.
B_018 12 Raw pressure value,
secondary variable 1,
secondary variable 2,
measured value (primary
variable), secondary
variable 3, output 1),
totalizer output 2)
Bad,
Sensor error, limit
value violated
Positive pressure too
high. High control limit
violated (>120% of
nominal measurement
range).
Reduce the pressure.