Operator control functions via PROFIBUS
7.4 Settings
SITRANS P DS III with PROFIBUS PA
110 Operating Instructions, 06/2013, A5E00053276-07
Start of scale value:
Full scale value:
as in "working range"
as in "working range"
>
>
>
Output scaling
Unit:
Start of scale value:
Full scale value:
as in "working range"
as in "working range"
as in "working range"
You can also adjust the output to another process value. Assign the required unit to the
parameters under the rubric output scaling. Assign the start of scale and full scale values
according to the measured value scaling.
Mass measurement
Start SIMATIC PDM. The measurement of mass is calculated from the volume and
density. Therefore create an assignment between the pressure to be measured
(measuring range) and the volume to be recorded (working range) by setting the following
parameters:
>
Input
>
>
Transducer block 1
Transmitter type:
Volume
>
>
>
Measuring range
Start of scale value
Full scale value
>
>
>
Working range
Unit:
Unit of volume [m
3
, dm
3
, cm
3
, mm
3
, l ...]
Start of scale value
Full scale value
If there is no linear relationship between level and volume in your container, you can also
define a characteristic curve:
>
Input
>
>
Transducer block 1
Transmitter type:
Volume
>
>
>
Characteristic curve
Characteristic curve
type:
User
-defined table
>
>
>
Nodes
New number of
nodes:
max. 31
x[n] measurement
range:
Pressure value
y[n] working range:
Corresponding volume value