Operator control functions via PROFIBUS
7.4 Settings
SITRANS P DS III with PROFIBUS PA
110 Operating Instructions, 06/2013, A5E00053276-07
Start of scale value:
Full scale value:
Start of scale value:
Full scale value:
You can also adjust the output to another process value. Assign the required unit to the
parameters under the rubric output scaling. Assign the start of scale and full scale values
according to the measured value scaling.
● Start SIMATIC PDM. The measurement of mass is calculated from the volume and
density. Therefore create an assignment between the pressure to be measured
(measuring range) and the volume to be recorded (working range) by setting the following
parameters:
Start of scale value
Full scale value
3
3
3
3
● If there is no linear relationship between level and volume in your container, you can also
define a characteristic curve:
Characteristic curve
type:
-defined table
Corresponding volume value