Configuration/project engineering
9.2 Configuring
SITRANS P DS III with PROFIBUS PA
160 Operating Instructions, 06/2013, A5E00053276-07
Analog input function block
The
Analog input function block
provides the content of the "Output" parameter. The
Totalizer function block
provides the content of the "Totalizer output" parameter. You can
select in the configuration which function block is used to generate the output data:
Output
Totalizer output
In the "Totalizer output" parameter you can insert the following additional functions:
Reset totalizer output
Operating mode
Using "Reset totalizer output" you can reset the integrator from the application program, and
with "Operating mode" you can determine its function.
Note
For STEP 7, the configuration tool is HW Config.
For STEP 5, the configuration tool is COM_PROFIBUS.
User data
Table 9- 1 User data dependent on the selected function block
Function block /
parameter
Byte
User data,
sent to master
User data,
sent from master
Meaning,
depending on parameter
Analog
input/output
1-4
Measured value
--- Pressure, height, volume, mass
flow, volume flow, sensor
temperature, electronics
temperature
5. Status
Totalizer / totalizer
output
6-9
Measured value
--- Mass or volume
5
Status
Table 9- 2 User data, dependent on selected additional function in the totalizer output function block
Additional function
Byte
User data,
sent to master
User data,
sent from master
Meaning
Reset totalizer
output
1 --- Reset totalizer
output
Totalizer reset function
0
Normal operation of totalizer
Integration running.
1
Step integration and reset
integrator back to 0.
2
Stop integration and load
integrator with preset value.