Technical data
13.2 Input point
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
195
Absolute pressure input (from the gauge pressure series)
PROFIBUS PA and FOUNDATION Fieldbus
Span (continuously
adjustable) or measuring
range, maximum
operating pressure (as
per 97/23/EC pressure
device guideline) and
maximum test pressure
(as per DIN 16086)
Span Maximum
operating
pressure
Maximum test
pressure
Measuring
range
Maximum
operating
pressure
Maximum test
pressure
8.3 …
250 mbar a (3
1.5 bar a
(21.8 psi a)
6 bar a
(87 psi a)
250 mbar a
(100 inH
2
O)
1.5 bar a
(21.8 psi a)
6 bar a
(87 psi a)
43 …
1300 mbar a
(17 ...
2.6 bar a
(37.7 psi a)
10 bar a
(145 psi a)
1.3 bar a
(18.9 psi a)
2.6 bar a
(37.7 psi a)
10 bar a
(145 psi a)
160 …
5000 mbar a
(2.32 …
10 bar a
(145 psi a)
30 bar a
(435 psi a)
5 bar a
(72.5 psi a)
10 bar a
(145 psi a)
30 bar a
(435 psi a)
1 … 30 bar a
(14.5 …
45 bar a
(653 psi a)
100 bar a
(1450 psi a)
30 bar a
(435 psi a)
45 bar a
(653 psi a)
100 bar a
(1450 psi a)
• Measuring cell with
silicone oil filling
0 mbar a (0 psi a)
• Measuring cell with
inert liquid
for process
temperature -20°C <
ϑ ≤ 60°C (-4°F < ϑ
30 mbar a (0.44 psi a)
for process
temperature 60°C <
ϑ ≤ 100°C (max.
85°C for measuring
cell 30 bar) (140°F <
ϑ ≤ 212°F (max.
185°F for measuring
30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C
(0.44 psi a + 0.29 psi a • (ϑ - 108 °F)/°F)
Upper measuring limit 100% of max. span (max. 100 bar g
(1450 psi g) for oxygen measurement)
ambient temperature/process temperature
60°C
100% of max. measuring range (max.
100 bar g (1450 psi g) for oxygen
measurement) ambient temperature/process
temperature 60°C
Start of scale value Between the measuring limits (fully adjustable)