Technical data
13.2 Input point
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
197
Differential pressure and flow rate input
PROFIBUS PA and FOUNDATION Fieldbus
Differential pressure and flow rate
Span (continuously
adjustable) or measuring
range and max. operating
pressure (in accordance
with 97/23/EC Pressure
Equipment Directive)
Span Maximum operating
Measuring range Maximum operating
1 … 20 mbar (0.4015
32 bar (464 psi) 20 mbar
32 bar a (464 psi)
1 … 60 mbar (0.4015
160 bar (2320 psi) 60 mbar
160 bar (2320 psi)
2.5 … 250 mbar
(1.004 …
250 mbar
(100.4 inH
2
O)
6 … 600 mbar
(2.409 … 240.9 inH
2
600 mbar
(240.9 inH
2
O)
16 … 1600 mbar
(6.424 …
2
1600 mbar
(642.4 inH
2
O)
50 … 5000 mbar
(20.08 …
2
5 bar
(2008 inH
2
O)
0.3 … 30 bar
30 bar
2.5 … 250 mbar
(1.004 …
2
420 bar (6091 psi) 250 mbar
(100.4 inH
2
O)
420 bar (6091 psi)
6 … 600 mbar
(2.409 … 240.9 inH
2
600 mbar
(240.9 inH
2
O)
16 … 1600 mbar
(6.424 …
2
1600 mbar
(642.4 inH
2
O)
50 … 5000 mbar
(20.08 …
2
5 bar
(2008 inH
2
O)
0.3 … 30 bar
30 bar
Lower measuring limit
• Measuring cell with
silicone oil filling
-100% of max. measuring range
(-33 % for 30 bar (435 psi) measuring cell) or 30 mbar a (0.44 psi a)
• Measuring cell with
inert liquid