EasyManua.ls Logo

Siemens SITRANS P DS III - Page 203

Siemens SITRANS P DS III
256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
13.4 Measuring accuracy
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
203
Absolute pressure measuring accuracy (from gauge and differential pressure series)
HART
PROFIBUS PA and FOUNDATION
Fieldbus
Reference conditions
Rising characteristic curve
Start of scale 0 bar
Seal diaphragm stainless steel
Measuring cell with silicone oil filling
Room temperature 25 °C (77 °F)
Measuring span ratio r
r = max. measuring span/set
measuring span
Measurement deviation with limit
setting, including hysteresis and
repeatability
Linear characteristic curve
0.1%
r ≤ 10
0.1%
10 < r ≤ 30
0.2%
Settling time T
63
without electrical
damping
Approx. 0.2 s
Long-term drift at ±30 °C (±54 °F)
per year ≤ (0.1 • r) %
per year ≤ 0.1 %
Effect of ambient temperature
in percent
At -10 … +60 °C (14 … 140 °F)
(0.1 • r + 0.2) % 0.3%
at -40 … -10°C and
+60 … +85°C
(-40 … 14°F and 140 … 185°F)
(0.1 • r + 0.15) % per 10 K ≤ 0.25 % per 10 K
Effect of mounting position In pressure per change of angle
for absolute pressure (from the gauge pressure series): 0.05 mbar
(0.000725 psi) per 10° inclination
for absolute pressure (from the differential pressure series): 0.7 mbar
(0.001015 psi) per 10° inclination
Correction via zero offset
Effect of auxiliary power supply In percent per change in voltage
0.005 % per 1 V
Measured-value resolution
3 • 10
-5
of the rated measuring range

Table of Contents

Other manuals for Siemens SITRANS P DS III

Related product manuals