Technical data
13.9 PROFIBUS communication
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
219
PROFIBUS PA communication
Function blocks
2
Analog input
Adaptation to user-specific process variable
Yes, linearly rising or falling characteristic
Adjustable electrical damping
0 ... 100 s
Simulation function
Output/input
Failure response Can be parameterized:
Last good value
Substitute value
Faulty value
Limit monitoring
Upper and lower warning and alarm limits
Totalizer Can be reset and preset
Selectable counting direction
Simulation function of totalizer output
Failure response Can be parameterized:
Addition with last good value
Stop addition
Addition with faulty value
Limit monitoring
Upper and lower warning and alarm limits
Physical block
1
Transducer blocks
2
Transducer block "Pressure"
Calibration by applying two pressures
Yes
Monitoring of sensor limits
Yes
Input of a container characteristic
With max. 30 interpolation points
Characteristic curve
Linear
Square-root
Not for gauge and absolute pressures
Low-flow cut-off and starting point of square-
rooting
Not for gauge and absolute pressures
Parameterizable
Simulation function
Pressure measurement Constant value
Parameterizable ramp function
Sensor temperature Constant value
Parameterizable ramp function
Transducer block "Electronics temperature"
Simulation function