Installing / mounting
4.5 "Remote seal" installation
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
55
Installation type for gauge pressure and level measurements (open containers)
Pressure transmitter above the
measuring point
MA
= ρ
FL
* g * H
U
+ ρ
oil
* g * H
1
-scale value:
ME
= ρ
FL
* g * H
O
+ ρ
oil
* g * H
1
Pressure transmitter below the
measuring point
MA
= ρ
FL
* g * H
U
- ρ
oil
* g * H
1
-scale value:
ME
= ρ
FL
* g * H
O
- ρ
oil
* g * H
1
1
≤ 7 m (23 ft); with halocarbon oil as the filling liquid, only H
1
MA
ME
FL
Density of the process medium in the container
oil
Density of the filling oil in the capillary line of the remote seal
Acceleration due to gravity
O
1
Distance between the container flange and the pressure transmitter
For absolute pressure measurements (vacuum), install the measuring device at least at the
height of the remote seal or below it (see installation types C).