Connecting up
5.1 Basic safety instructions
SITRANS P DS III with PROFIBUS PA
64 Operating Instructions, 06/2013, A5E00053276-07
Danger of explosion in hazardous areas due to voltage flashover.
• Connect the device to an extra-low voltage with safe isolation (SELV).
Lack of equipotential bonding
Danger of explosion through compensating currents or ignition currents through lack of
equipotential bonding.
• Ensure that the device is potentially equalized.
: It may be permissible to omit connection of the equipotential bonding for devices
with type of protection "Intrinsic safety Ex i".
Danger of explosion through unprotected cable ends in hazardous areas.
• Protect unused cable ends in accordance with IEC/EN 60079-14.
Improper laying of shielded cables
Danger of explosion through compensating currents between hazardous area and the non-
hazardous area.
• Only ground shielded cables that run into the hazardous area at one end.
• If grounding is required at both ends, use an equipotential bonding conductor.
Connecting device in energized state
Danger of explosion in hazardous areas.
• Connect devices in hazardous areas only in a de-energized state.
:
• Circuits of limited energy may also be connected in the energized state in hazardous
areas.
• Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the
relevant certificate