Operation
6.5 Local operation
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
89
Display
Meaning
[2]
Exchangeable for previous SITRANS P/PA device
[128] Profile-compliant:
Exchangeable for transmitter with PROFIBUS PA Profile 3.0 with:
Analog input function block
Totalizer.
Procedure
To change the device mode, proceed as follows:
1. Set mode 16.
The current operation type "0", "1", "2" or "128" appears in the measured value display.
2. Select the device mode.
The local operation type must match the operation type in PROFIBUS.
3. Save with the [M] button.
Note
Each device operation type is as
signed a particular device master data file (GSD file).
If the configuration of your PROFIBUS
-PA strand does not correspond to the device
mode selected, the device will not start periodic data exchange. Successful establishment
of communic
ation is identified by the indicator "o" at the top left of the display.
Note
If the device is exchanging period data, no change is possible to the device operating
type.
Table 6- 18 Device master data file
Display
File name
[0]
pa_29700.gsd or pa_39700.gsd
[1]
siem80A6.gsd
[2]
sip1804B.gsd
[128]
pa_29740.gsd or pa_39740.gsd
See also
Errors (Page 188)