4100ES-S1 Programming Guide Document: LT0400
Appendices
12-10
12.3.2 Alarm / Fault / Normal Test Button and LEDs
This button is used to select between Alarm Test, Fault Test and Normal operation for the
Multifunction buttons. The Alarm Test and Fault Test LEDs indicate what operation the
Multifunction buttons will initiate if pressed.
The Alarm and Fault Test code is stored in a separate Program to all other code. This
Program is enabled only if the panel is in Alarm or Fault Test mode.
References:
Push Button Mode set to “PBH” Mode
Point Address: 0-5-1 Alarm Fault Test Normal (AFN) Button
P513 Status of AFN button
0-5-6 Alarm Test LED
P514 Active if panel is in Alarm Test Mode
0-5-13 Fault Test LED
P515 Active if panel is in Fault Test Mode
Equations:
3-12 Alarm Test Mode
[INPUTS]
STATUS ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND NOT STATUS ON
P514 | DIGITAL | UTILITY | ALARM TEST
AND NOT STATUS ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD ON PRI=9,9
P514 | DIGITAL | UTILITY | ALARM TEST
HOLD ON PRI=9,9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD OFF PRI=9,9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
PRINT PANEL "ALARM TEST READY-PRESS FOR FAULT TEST"
HOLD ON PRI=7,7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-13 Fault Test Mode
[INPUTS]
STATUS ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND STATUS ON
P514 | DIGITAL | UTILITY | ALARM TEST
AND NOT STATUS ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD ON PRI=9,9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD OFF PRI=9,9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
HOLD OFF PRI=9,9
P514 | DIGITAL | UTILITY | ALARM TEST
PRINT PANEL "FAULT TEST READY-PRESS AGAIN FOR NORMAL"
[END OUTPUTS]