Document: LT0400 4100ES-S1 Programming Guide
About the Programming Tools
3.5 Steps to Configuring a New System
The steps to configuring a new system are covered in Sections 4 -10.
Section 11 contains details on “building” the configuration and downloading it into the panel.
3.6 Upgrading an Existing Configuration
The configuration must be prepared/edited using a version of the programmer that matches
the Panel Exec firmware installed. If the panel Exec firmware is updated, e.g., to add some
new features, then the configuration will need to be upgraded using the new compatible
programmer version and downloaded to the panel after the firmware has been updated.
A panel with a non-matching configuration will report that the existing configuration is an
incompatible version and repeatedly restart. The upgraded version of the configuration must
be downloaded before normal operation will resume.
Locate the existing database file (job *.SDB4100U) for this system. If you want to keep the
old version as well as the upgraded version of the configuration, you may open it using the
old Programmer - do a ‘Save As’/’Copy...’ and enter a new job name for the upgraded
version, or simply copy the entire directory of the old configuration to a backup directory.
Open the database file using the Programmer with the new version required. The
Programmer will identify that the database is an older version and will prompt to do an
upgrade.
Click on the Yes button. This will upgrade the database to the format for the new
programmer version.
With the introduction of 4100U version 12
firmware, and for all 4100ES-S1 versions,
the Australian message library (part number
SF0457) is loaded as a Primary message
library.
Select the Panel tab and then System
Options tab and ensure the setting for
Language of Use’ is set to ‘Primary.
This will be set correctly in all the new
configuration templates.
Make any other changes required, save the new database, build it and download it to the
panel as described in section 11.

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals