Document: LT0400 4100ES-S1 Programming Guide
Appendices
12-9
12.3.1 Common Zone Alarm LED
This Red LED flashes if any Zone is in alarm and is not acknowledged.
The LED is on steady if any Zone is in Alarm and all Alarms are acknowledged.
The LED is off when there are no Zones in Alarm.
References
Point address: 0-5-11 Common Zone Alarm LED
Equations:
3-9 Common Fire Alarm LED Flash
[INPUTS]
STATUS ON
P11 | DIGITAL | UTILITY | UNACKNOWLEDGED FIRE ALARM EXISTS
AND STATUS ON
L256 | LIST | DPSEUDO | BRIGADE CALL ALARM LIST
AND STATUS ON
P512 | DIGITAL | UTILITY | A ZONE ALARM LED IS FLASHING
[END INPUTS]
[OUTPUTS]
FLASH SLOW
0-5-11 | MKYLED5CRY | LEDRED | COMMON ALARM LED
[END OUTPUTS]
3-10 Common Fire Alarm LED Steady
[INPUTS]
STATUS ON
A0 | ANALOG | ANALOG | NUMBER OF SYSTEM FIRE ALARMS
AND NOT STATUS ON
P512 | DIGITAL | UTILITY | A ZONE ALARM LED IS FLASHING
[END INPUTS]
[OUTPUTS]
FLASH ON
0-5-11 | MKYLED5CRY | LEDRED | COMMON ALARM LED
[END OUTPUTS]
3-11 Common Fire Alarm LED Off
[INPUTS]
NOT STATUS ON
A0 | ANALOG | ANALOG | NUMBER OF SYSTEM FIRE ALARMS
[END INPUTS]
[OUTPUTS]
FLASH OFF
0-5-11 | MKYLED5CRY | LEDRED | COMMON ALARM LED
[END OUTPUTS]

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals