4100ES-S1 Programming Guide Document: LT0400
Addressable Device Settings
6-4
6.3.3 4090-9002 Relay IAM
Device Type
RIAM Standard Setting
Point Type
RELAY General Purpose relay.
TRELAY Fault Relay on until fault cleared
6.3.4 4090-9007 Signal ZAM
Device Type
SIGIAM Signal IAM - IDNet
Point Type
RELAY General Purpose Supervised relay (under Custom Control).
SIGNAL Alarm Relay on until Alarm is cleared
6.3.5 4090-9101 Monitor ZAM
Device Type
MBZAM Standard Setting
Point Type
FIRE Standard setting
6.3.6 4190-9050 4-20mA Analog Monitor ZAM
Device Type
ANAMON Standard Setting
Point Type
The Point Types are custom configurable using the AMON Pt Type Tab. The Point
types need to be configured before the 4190-9050 is added.
6.3.7 4090-9118 Relay IAM with T-Sense Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
TRIAM Standard setting
Point Type
UTILITY Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY Fixed Device type
Point Type
RELAY General Purpose relay
TRELAY Fault Relay on until fault cleared

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals