Document: LT0400 4100ES-S1 Programming Guide
Appendices
12.4.2 Lists
Zone 1
L261 – Zone 1 Alarm List
L262 – Zone 2 Alarm List
…
L260+n – Zone n Alarm List
12.4.3 Switches and LEDs
Zone 1
3-65 – Zone 1 Multifunction Switch
3-1 – Zone 1 Alarm LED
3-2 – Zone 1 Isolated LED
12.4.4 Zone 1 Equations
4-2 ZONE 1 Isolate Switch
[INPUTS]
STATUS ON
P901 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 1
AND NOT STATUS ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
AND NOT STATUS ON
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD ON PRI=9,9
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
HOLD ON PRI=9,9
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
[END OUTPUTS]
4-3 ZONE 1 De-Isolate Switch
[INPUTS]
STATUS ON
P901 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 1
AND STATUS ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
AND NOT STATUS ON
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
HOLD ON PRI=9,9
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
[END OUTPUTS]
4-4 ZONE 1 Isolate Stops Fire
[INPUTS]
STATUS FIRE
L261 | LIST | MIXED | ALARM LIST ZONE 1
AND NOT STATUS ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P801 | DIGITAL | UTILITY | ALARM ZONE 1
[END OUTPUTS]