EasyManuals Logo

Simplex 4100ES-S1 Programming Guide

Simplex 4100ES-S1
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Document: LT0400 4100ES-S1 Programming Guide
Addressable Device Settings
Mx-x-2 2
nd
Sub Point (T-Sense input)
Device Type
MTSENSE Fixed Device type
Point Type
FIRE General Fire Point
UTILITY Input used by Custom Control Logic only
TROUBLE Input used to indicate a Fault status
WATER Sprinkler -Flow Switch setting
WSO Sprinkler Flow Switch and Valve Monitor
6.3.8 4090-9119 Relay IAM with Unsupervised Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
FRIAM Standard setting
Point Type
UTILITY Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY Fixed Device type
Point Type
RELAY General Purpose relay
TRELAY Fault Relay on until fault cleared
Mx-x-2 2
nd
Sub Point (feedback input)
Device Type
MFEEDBK Fixed Device type
Point Type
UTILITY Input used by Custom Control Logic only
TROUBLE Input used to indicate a Fault status

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals