Document: LT0400 4100ES-S1 Programming Guide
Addressable Device Settings
6.2.4 4098-9754E Multi-Sensor Photo Heat Detector (COMBO)
Mx-x-0 Parent Point
Device Type
COMBO – Standard Multi-Sensor detector on standard base
ICOMBO – Standard Multi-Sensor detector on Isolator base
SCOMBO – Standard Multi-Sensor detector on Sounder base
Mx-x-1 1
st
Sub Point
Device Type
MPHOTO – Standard setting
Point Type – Photo Part
SMOKE – Standard setting
VSMOKE – Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
DUCT – Duct detector
Mx-x-2 2
nd
Sub Point
Device Type
MHEAT – Standard setting
Point Type – Heat Part
MHEAT – Standard setting
MOHEAT – Standard heat detector with Rate of Rise
Mx-x-3 3
rd
Sub Point
Device Type
MARCOR WARNING: DO NOT USE THIS SETTING SINCE THIS IS NOT
APPROVED IN AUSTRALIA – USE MAOFF INSTEAD
MAOFF – Choose this setting for Australian use.
Point Type – R-Correlation Part
UTILITY – Standard setting for MAOFF
6.3 Addressable Device Settings
Any unused points should be set as utility to avoid potential false alarms from unused fire
point type inputs.
6.3.1 4099-9032 MCP
Device Type
KACPULL – Standard MCP
Point Type
PULL – Standard setting
6.3.2 4090-9001/4090-9051 Supervised Input IAM
The 4090-9051 is an encapsulated version of the 4090-9001, with wire leads instead of
terminals. Programming and performance are identical.
Device Type
IAM – Standard setting
Point Type
FIRE – General Fire Point.
UTILITY – Input used by Custom Control Logic only
TROUBLE – Input used to indicate a Fault status