4100ES-S1 Programming Guide Document: LT0400
Addressable Device Settings
6-6
6.3.9 4090-9120AU 6 Point I/O Module (4 Inputs, 2 Relay outputs)
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
MLPTIO – Standard setting
Point Type
UTILITY – Standard setting
Mx-x-1 to Mx-x-4 Sub Points (input)
Device Type
MINPUT – Fixed Device type
Point Type
FIRE – General Fire Point.
UTILITY – Input used by Custom Control Logic only e.g., fan control inputs
TROUBLE – Input used to indicate a Fault status
Mx-x-5 and Mx-x-6 Sub Points (relay outputs)
Device Type
MOUTPUT – Fixed Device type
Point Type
RELAY – General Purpose relay
TRELAY – Fault Relay on until fault cleared
6.3.10 4090-9116 Addressable IDNET Isolator
Device Type
IDNETISO – Standard Setting
Point Type
ISO – Standard setting
6.3.11 4090-9117AU Addressable IDNET Power Isolator
Device Type
POWERISO – Standard Setting
Point Type
ISO – Standard setting