4100ES-S1 Programming Guide Document: LT0400
Appendices
12-6
Equations:
3-7 Alarm Verification Timing / Start up
[INPUTS]
STATUS ON
A34 | ANALOG | TIMER | SYSTEM STARTUP PULSE TIMER
[END INPUTS]
[OUTPUTS]
SET CONSTANT 5 CNTS
A37 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - RETARD TIME
SET CONSTANT 10 CNTS
A38 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - RESET TIME
SET CONSTANT 180 CNTS
A39 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - CONFIRMATION TIME
HOLD OFF PRI=7,7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
HOLD ON PRI=7,7
P478 | DIGITAL | UTILITY | INHIBIT DEVICE TROUBLES WHILE DISABLED
[END OUTPUTS
12.2.7 Brigade Relay Equations
The following are the equations used to drive the Alarm, Isolate and Fault Brigade Relays. These
equations should not be modified without consulting a TFPP/Simplex Technician.
References:
Point Address:
0-7-3 City Alarm Relay (relay on 4100+ type CPU motherboard)
0-7-4 City Trouble Relay (relay on 4100+ type CPU motherboard)
1-9 City Fire/Opt Relay 1 (Alarm relay on SPS piggyback board)
1-11 City SUPV/Opt Relay 2 ( Supervisory / Isolate relay on SPS piggyback board
1-12 City Fire/Opt Relay 3 (Trouble relay on SPS piggyback board)
A1 Number of Isolates on Panel
A2 Number of Faults on Panel
L256 Brigade Call Alarm List
3-1 ASE Alarm Relay
[INPUTS]
STATUS ON
L256 | LIST | DPSEUDO | BRIGADE CALL ALARM LIST
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=7,7
0-7-3 | MCODE7 | RELAY | Master Output - City Alarm Relay
TRACK ON PRI=7,7
1-9 | SPECOUT | SPECOUT | CITY FIRE/OPT RELAY 1
[END OUTPUTS]
3-2 ASE Isolate Relay
[INPUTS]
STATUS ON
A1 | ANALOG | ANALOG | NUMBER OF SYSTEM SUPERVISORIES
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=7,7
1-11 | SPECOUT | SPECOUT | CITY SUPV/OPT RELAY 2
[END OUTPUTS]