4100ES-S1 Programming Guide Document: LT0400
Building and Downloading the Configuration
11-10
You can upload a job to your PC and perform a Full Compare, to see all the differences
between the configurations:
1. Click on the Upload Jobs and Full Compare button.
2. This will upload the file to the PC and will launch the database compare tool that
comes with the ES Programmer.
11.6 Serial File Transfer (4100U and older systems)
IMPORTANT: Serial File Transfer can be used with 4100ES-S1 systems. However, this
will not update the Compact Flash or access files stored there, and will not produce
History snapshots in the Compact Flash. Serial Transfer should only be used for
direct transfer of InfoAlarm files, if this becomes necessary.
Serial file transfer for CFIG, slave, network or bootloader files should only be used
with 4100ES-S1 when there is a problem with IP File Transfer.
11.6.1 Starting the Serial Transfer Utility
The Serial File Transfer utility can be started from within the ES Programmer.
When the Programmer is already running,
click on the Transfer menu, located along
the menu bar at the top of the programmer
window.
When the options appear, click on Serial,
and the select the connection you want to
make:
to Panel... is the usual option for
normal use with 4100ES-S1.
The File Transfer Utility appears: