4100ES-S1 Programming Guide Document: LT0400
Appendices
12-18
4-5 ZONE 1 New Alarm and LED Flash
[INPUTS]
CONTINUE
AND STATUS FALMACK
L261 | LIST | MIXED | ALARM LIST ZONE 1
[END INPUTS]
[OUTPUTS]
FLASH SLOW
3-1 | LED | LED | AZF1 LED
TRACK ON PRI=9,9
P512 | DIGITAL | UTILITY | A ZONE ALARM LED IS FLASHING
[END OUTPUTS]
4-6 ZONE 1 Ackāed Alarm and Steady LED
[INPUTS]
NOT STATUS FALMACK
L261 | LIST | MIXED | ALARM LIST ZONE 1
OR STATUS ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
AND STATUS FIRE
L261 | LIST | MIXED | ALARM LIST ZONE 1
[END INPUTS]
[OUTPUTS]
FLASH ON
3-1 | LED | LED | AZF1 LED
[END OUTPUTS]
4-7 ZONE 1 Alarm LED Off
[INPUTS]
NOT STATUS FIRE
L261 | LIST | MIXED | ALARM LIST ZONE 1
[END INPUTS]
[OUTPUTS]
FLASH OFF
3-1 | LED | LED | AZF1 LED
[END OUTPUTS]
12.4.5 Zone n Equations
ZONE n Isolate Switch
[INPUTS]
STATUS ON
P900+n | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE n
AND NOT STATUS ON
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
AND NOT STATUS ON
P700+n | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE n
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD ON PRI=9,9
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
HOLD ON PRI=9,9
P700+n | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE n
[END OUTPUTS]
ZONE n De-Isolate Switch
[INPUTS]
STATUS ON
P900+n | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE n
AND STATUS ON
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
AND NOT STATUS ON
P700+n | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE n
AND RECALL 8
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
HOLD ON PRI=9,9
P700+n | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE n
[END OUTPUTS]