Chapter 3 Alarm Indication and Troubleshooting
HRS Series 3.3 Troubleshooting
3-89
9. Check the compressor.
Perform the checks after leaving the Thermo-Chiller not operating for 2 hours or more (after the
compressor body temperature has decreased enough).
Disconnect the connector "CN4" of the power board to which the fan/compressor cable is
connected.
Check the electricity continuity between the cable connector pin number 2 and the pin number 4 with
a tester.
<Normal> Electric continuity between the cable connector pin number 2 and the pin number 4: Yes
Fig. 3.3-65 Check the compressor