HRX-MM-N007
Chapter 4 Service Procedure
4.2 Work Procedure HRS Series
4-6
<For the water-cooled refrigeration chiller, drain the facility water according to the
procedures from 6 to 8.>
6. Remove the piping of the outlet of the facility water.
7. Remove the dustproof filter to remove the plug.
Please refer P4-33 for the procedure of removal.
Fig. 4.2-4 Removal of plug
8. After ensuring that the facility water is completely discharged, apply the sealant tape to the
plugs which are removed during step 7 for mounting.
Mount the dustproof filter after mounting them. Please refer P4-33 for how to mount.
Just removing the facility water piping does not discharge the facility
water completely. Remove the plug to discharge the facility water.
Plug
Dustproof filter

Table of Contents