HRX-MM-N007
Chapter 4 Service Procedure
4.5 Replacement Procedure HRS Series
4-20
Mounting
1. Mount the pump. (Screw ×4)
2. Mount the hose. (2 pcs.)
Tightening torque of hose between high pressure pump and circulating fluid outlet
3. Connect the ground cable (G4). (Screw ×1)
4. Mount pump cable to the power board.
5. Mount the support panel. (Screw ×2)
6. Mount the upper panel and the right panel in reversed order of removal.
HRS-A/W-20-T
Table 4-9 Part number of service parts (High pressure pump)
Description
Part number
High pressure pump (For 200V type option T)
HRS-S0062
High pressure pump (For HRS030 option T)
HRS-S0299
High pressure pump (For 200V type option MT)
HRS-S0063
High pressure pump (For HRS030 option MT)
HRS-S0300
Removal
1. Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2. Remove the upper panel and the side panel on the right referring the 4.2.1 Removal and
the mounting of the panel.
3. Remove the support panel. (Screw ×4)
4. Remove the connector of the pump cable from the power board.
Be sure to shut off the breaker of the facility power supply (the user’s
machine power supply) before replacement work.