EasyManua.ls Logo

SUNSTONE CDDP-A - Using Modbus Poll; Setup a Connection; Reading Coils

SUNSTONE CDDP-A
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Questions? Call or Text +1-801-658-0015 • 43
e Micro Welder Experts
Using Modbus Poll
The second piece of software that can be used to control the
CDDP-A is Modbus Poll, a good example of a program that
continues to poll information from/to the CDDP-A. Paid and trial
versions of the Modbus Poll are available at https://www.mod-
bustools.com/download.html
After you’ve installed Modbus Poll, following these instructions
to connect to and control the CDDP-A welder.
SETUP A CONNECTION
Click on the Connection menu to display the
Connection Setup window, as shown in Figure 42.3.
Select Modbus TCP/IP from the Connection menu.
Retain the Serial Settings defaults.
Input the CDDP-A’s IP address into the IP Address or
Node Name space.
Click the OK button to save the settings.
READING COILS
Coils are names for memory addresses, or pre-dened variable
names. In short a coil is a boolean (bit) variable. Follow these
instructions on how to access coils.
Click on the Setup menu and choose Read/Write Deni-
tion. The Read/Write Denition window will appear. See
Figure 43.1.
In the Read/Write Denition window, click on 01 Read
Coils in the Function drop down menu box.
Change the Quantity to 24.
Verify the Read/Write Disabled box is unchecked. With
the Read/Write Disabled box not checked, the software
will continue to poll the inputs every one second.
Click the Apply button.
Click the OK button to accept all changes.
In the Modbus Poll main window (see Figure 43.2), coil 0x0000 is
on the top left and has a value of 0, so Pulse 1 Power Compara-
tor Enable is O “0x00”. Further down that column you will see
Figure 43.1. Read/Write Denition window.
Figure 43.2.
Figure 43.3.

Table of Contents

Related product manuals