EasyManua.ls Logo

SUNSTONE CDDP-A - Using Simply Modbus TCP Client; Setup a Connection; Reading a Coil

SUNSTONE CDDP-A
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 • Questions? Call or Text +1-801-658-0015
SUNSTONE CDDP-A USERS GUIDE
Using Simply Modbus TCP Client
As previously noted, the third piece of software to control the CDDP-A via an Ethernet connection is Simply
Modbus, which can be downloaded at https://www.simplymodbus.ca/TCPclient.htm. The free edition will allow
up to six messages before you will need to restart application as of when this users guide went to press.
SETUP A CONNECTION
To connect the CDDP-A to the Simply Modbus TCP Client software, refer to Figure 46.1 and follow these in-
structions:
Set Mode (A) to TCP.
Enter the CDDP-A’s IP address (B).
Make sure the Port (C) is 502, which is the default port value.
Click on the Connect button (D). The Not Connected indicator (E) should change to Connected and turn
green.
READING A COIL
To read from a coil, and with the CDDP-A connected, refer to Figure 47.1 and follow these instructions:
Verify the Slave ID is 1.
Verify the value of the First Coil address is 40000.
A B C
D
Figure 46.1. Download the Simply Modbus
TCP Client software and then connect to the
CDDP-A. Use the TCP mode, enter the CDDP-
A’s IP address, make sure the Port is 502, and
then click on the Connect button. When the
CDDP-A is connected, the Not Connected
button with change to green and indicate
Connected.
E
F

Table of Contents

Related product manuals