UDL & Digi Options Premier Elite 24,24-W, 48,48-W, 88, 168 & 640 Installation Manual
102 INS176-9
Non-Zone Event Types
The default Non-Zone Event codes are as follows:
No Type Event Reporting Group Contact ID SIA ID
22 Keypad Medical Alarm Priority Alarm 100 MA Keypad No *
Restore Restore 100 MH Keypad No *
23 Keypad Fire Alarm Priority Alarm 115 FA Keypad No *
Restore Restore 115 FH Keypad No *
24 Keypad Audible PA Alarm Priority Alarm 120 PA Keypad No *
Restore Restore 120 PH Keypad No *
25 Keypad Silent PA Alarm Priority Alarm 122 PA Keypad No *
Restore Restore 122 PH Keypad No *
26 Duress Code Alarm Alarm Priority Alarm 121 HA User No
Restore Restore - 122 HH User No
27 Alarm Active Alarm Not Reported - - -
Restore Not Reported - - -
28 Bell Active Alarm Not Reported - - -
Restore Not Reported - - -
29 Zones Locked Out Alarm Alarm 130 BA Zone No
Restore Not Reported - - -
30 Verified Cross Zone Alarm Alarm Alarm 130 BV 00
Restore Not Reported - - -
31 User Code Alarm Not Reported - - User No
Restore Not Reported - - -
32 Exit Started Alarm Not Reported - - Keypad No
Restore Not Reported - - -
33 Exit Error (Arming Failed) Alarm Open/Close 457 EE 00
Restore Not Reported - - -
34 Entry Started Alarm Not Reported - - -
Restore Not Reported - - -
35 Area Arm Suite Alarm Open/Close - - Suite No 1 - 8
Restore Open/Close - - -
36 Armed with Line Fault Alarm Not Reported - - User No
Restore Not Reported - - -
37 Open/Close (Full Arm) Alarm Open/Close 401 OP User No
Restore Open/Close 401 CL User No
38 Open/Close (Part Arm) Alarm Open/Close 401 OP User No
Restore Open/Close 401 CL User No
39 Auto Open/Close Alarm Open/Close 403 OA 00
Restore Open/Close 403 CA 00
40 Auto Arm Deferred Alarm Open/Close 405 CE User No
Restore Open/Close - - -
41 Open After Alarm (Alarm Abort) Alarm Open/Close 406 OR 00
Restore Not Reported - - -
42 Remote Open/Close Alarm Open/Close 407 OP 00
Restore Open/Close 407 CL 00
43 Quick Arm Alarm Not Reported - - -
Restore Open/Close 408 CL Keypad No *
44 Recent Closing Alarm Open/Close 459 CR 00
Restore Not Reported - - -
45 Reset After Alarm Alarm Restore - - Reset ID ****
Restore Not Reported - - -
46 Power Output Fault Alarm Maintenance 300 YP Device ID **
Restore Restore 300 YQ Device ID **
47 AC Fail Alarm Maintenance 301 AT 00
Restore Restore 301 AR 00