4.8. TRANSFER FAIL ALARM RESET
Should a Transfer fail alarm occur, the flashing ALARM ICON will appear on the GHC Home
page as shown below. If the transfer switch is pre-programmed as Force Transfer, the ATS will
automatically transfer to the alternate source (if available) and will still stay locked onto the
alternate source unit the Transfer Fail alarm is manually reset by the ATS operator.
To determine which transfer alarm condition has been triggered, press the ALARM ICON to
navigate to the ALARMS Page as shown below. Once the specific alarm condition has been
determined and the necessary corrective action has been implemented, the alarm can be reset
by pressing the “RESET ALARMS” button.
4.9. TIMER BYPASS
The following automatic sequencing time delays can be temporarily bypassed when the time
function is active as shown on the TSC 900 GHC display:
• Utility Return Timer
• Cooldown Timer
• Warm up Timer
• Neutral Delay Timer
• Pre and Post Transfer Delay
This feature is typically used when testing to avoid waiting for the complete duration of the time
period. To activate the bypass function, press the BYPASS button when the timer is in operation
as displayed on the screen.
NOTE: The Time delay functions will return to the normal time settings on the subsequent
automatic operating sequence.