Fig. 33: Low overload
The high overload means that if 150% of the continuous current (I
H
) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 92% of I
H
or less. This is to
make sure that the output current is not more than I
H
during the duty cycle.
Fig. 34: High overload
For more information, refer to the standard IEC61800-2 (IEC:1998).
9.1.5 BRAKE RESISTOR RATINGS
Make sure that the resistance is higher than the set minimum resistance. The power
handling capacity must be sufficient for the application.
VACON · 106 TECHNICAL DATA, VACON® 100 INDUSTRIAL
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/