10.1.2 MAINS VOLTAGE 380-500 V
Table 45: The power ratings of VACON
®
100 FLOW in mains voltage 380-500 V, 50-60 Hz, 3~
Enclosure
size
Drive type Loadability Motor shaft power
Continuous
current
I
Lout
[A]
Input
current I
Lin
[A]
10%
overload
current [A]
Max
current I
S
2s
400 V
mains
480 V
mains
10%
overload
40°C [kW]
10%
overload
40°C [hp]
MR8 0140 140.0 139.4 154.0 210.0 75.0 100.0
0170 170.0 166.5 187.0 280.0 90.0 125.0
0205 205.0 199.6 225.5 340.0 110.0 150.0
MR9 0261 261.0 258.0 287.1 410.0 132.0 200.0
0310 310.0 303.0 341.0 502.0 160.0 250.0
MR10 0385 385.0 385.0 423.5 620.0 200.0 300.0
0460 460.0 460.0 506.0 770.0 250.0 350.0
0520 520.0 520.0 572.0 920.0 250.0 450.0
0590* 590.0 590.0 649.0 1040.0 315.0 500.0
MR12 0650 650.0 648.0 715.0 1180.0 355.0 500.0
0730 730.0 724.0 803.0 1300.0 400.0 600.0
0820 820.0 822.0 902.0 1460.0 450.0 700.0
0920 920.0 916.0 1012.0 1640.0 500.0 800.0
1040* 1040.0 1030.0 1144.0 1840.0 560.0 900.0
1180* 1180.0 1164.0 1298.0 1840.0 630.0 1000.0
VACON · 116 TECHNICAL DATA, VACON® 100 FLOW
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/