5 INSTALLATION INTO CABINET
5.1 GENERAL INFORMATION
The AC drives that are described in this manual have the enclosure class IP00. You must
install them in a cabinet or other enclosure that has a correct level of protection against the
ambient conditions in the installation area. Make sure that the cabinet gives protection
against water, humidity, dust and other contaminations.
The cabinet must also be sufficiently strong for the weight of the IP00 drive module and other
devices. Use a free-standing, floor-mounted cabinet made of sheet metal.
The enclosure class of the cabinet should be at least IP21 / UL Type 1. When you prepare the
installation, obey the local regulations.
5.1.1 GENERAL INFORMATION ABOUT THE INSTALLATION, MR8-MR9
C
A
B
DC+/R+
R-
PE W/T3V/T2U/T1
DC-
L1 L2 L3
W1V1U1PE
M
PE
L1
L2 L3PE
Fig. 12: The main circuit diagram, MR8 and MR9
A. The power unit
B. The control unit
C. The brake resistor for the optional brake
chopper
VACON · 30 INSTALLATION INTO CABINET
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals